EMC
The EMC behavior of the device is designed for applications in industrial environments as well as residential, commercial or small business environments.
The device was tested according to EN 61000-6-1, EN 61000-6-2, EN 61000-6-3 and EN 61000-6-4.
Without additional measures to reduce emissions at the output (e.g. by using a filter), the device is not suitable for supplying a local DC power network in residential, commercial or small business environments. There are no restrictions for local DC power networks in industrial environments.
EMC interference immunity |
| ||
|---|---|---|---|
Strong transients | VDE 0160 | Over the entire load range | 750V, 0.3ms |
EMC interference emission |
| |
|---|---|---|
Cable-related interference emission, input lines | EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 | Class B |
Interference emission | EN 55011, EN 55022 | Class B |
Harmonic input current | EN 61000-3-2 | Class A requirements met |
Voltage fluctuations, flicker | EN 61000-3-3 | Requirements met 1) |
This device complies with FCC Part 15. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must be able to deal with any interference received, including interference that may cause undesired operation. | ||
1) Tested with constant current loads, non-pulsating
Switching frequencies | ||
|---|---|---|
PFC converter | 100kHz | fixed frequency |
Main converter | 80kHz to 140kHz | Output load dependent |
Auxiliary converter | 60kHz | fixed frequency |