Safety instructions

Signal words

The signal words used in the documentation are classified below. In order to prevent injury and damage to persons and property, read and follow the safety and warning notices.

Personal injury warnings

DANGER

Hazard with high risk of death or serious injury.

WARNING

Hazard with medium risk of death or serious injury.

CAUTION

There is a low-risk hazard that could result in medium or minor injury.

Warning of damage to property or environment

Notice

The environment, equipment, or data may be damaged.

Information on handling the product

Safety instructions 1:

This information includes, for example:
recommendations for action, assistance or further information on the product.

Intended use

This device is designed for installation in a housing and is intended for general professional use, for example in industrial control systems or office, communication and measuring equipment.

Do not use this power supply in installations where a malfunction could cause serious injury or danger to human life.

Without additional measures to reduce conducted emissions at the output (e.g. by using a filter), the device is not suitable for supplying a local DC network in residential, commercial and light-industrial environments. No restrictions apply for local DC power networks in industrial environments.

Exclusion of liability

All the components are supplied in particular hardware and software configurations appropriate for the application. Modifications to hardware or software configurations other than those described in the documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG.

Personnel qualification

This description is only intended for trained specialists in control, automation and drive engineering who are familiar with the applicable national standards.

Safety regulations

Please note the following safety instructions and explanations!
Product-specific safety instructions can be found on following pages or in the areas mounting, wiring, commissioning etc.

Safety instructions and installation requirements for PS2001-2420-1001 power supply

DANGER

Danger of electric shock, fire, injuries, injuries resulting in death!

  • Do not use the power supply without proper grounding (protective conductor). Use the terminal at the input terminal strip for the ground connection, not one of the screws on the housing.
  • Turn power off before working on the device. Provide protection against unintentional reconnection.
  • Ensure proper wiring by following all local and national regulations.
  • Do not modify or repair the device.
  • Do not open the device, as high voltages are present inside.
  • Avoid foreign objects entering the housing.
  • Do not use in wet locations or in areas where moisture or condensation can be expected.
  • Do not touch the device when it is switched on or immediately after it has been switched off. Hot surfaces may cause burns.
Safety instructions 2:

Further notes on installation requirements

  • If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to the factory for inspection.
  • Install the device in a housing that provides protection against electrical, mechanical and fire hazards.
  • Install the device on a DIN rail according to EN 60715, with the input terminals on the bottom of the device.
  • The maximum ambient air temperature is +70°C (+158°F). The operating temperature is the same as the ambient or surrounding air temperature and is defined 2 cm below the device.
  • The device is designed for convection cooling and does not require an external fan. Do not obstruct the air flow or cover the ventilation grid!
  • Observe the following installation clearances (see table Minimum installation clearances):
  • 40 mm at the top, 20 mm at the bottom and 5 mm on the left and right are recommended if the device continuously runs at more than 50% of the nominal output.
  • Increase this distance to 15 mm if the device is loaded with more than 90% of the nominal output or if the adjacent device is a heat source (e.g. another power supply).
  • When the device is permanently loaded with less than 50%, the 5 mm can be reduced to zero.

Minimum installation clearances

Output power in relation to the nominal output

Minimum installation clearances (mm)

top

bottom

Left and right side

< 50%

40

20

0

≥ 50%

40

20

5

≥ 90%

40

20

15

Safety instructions 3:

Further notes on installation requirements (connection and wiring)

  • Ensure that the wiring is correct by following all local and national regulations.
  • Use suitable copper cables that are designed for a minimum operating temperature of:
    60°C at ambient temperatures up to 45°C
    75°C at ambient temperatures up to 60°C
    90°C at ambient temperatures up to 70°C
  • Ensure that all strands of a stranded wire enter the terminal connection.
  • Use ferrules for wires at the input terminals.
  • Unused screw terminals should be securely tightened.
  • The device is designed, tested and approved for branch-circuit currents up to 32 A (IEC) and 30 A (UL) without additional protection. If an external fuse is used, do not use circuit breakers smaller than 10 A (B or C characteristic) to avoid unwanted tripping of the circuit breaker.
  • The input can also be supplied by batteries or similar DC sources. The continuous voltage between the supply voltage and the PE/ground potential must not exceed 375 Vdc.
  • The device is designed to meet the requirements of protection class I according to IEC 61140.
  • Do not use without a proper PE connection (protective earth).
  • An isolating device must be provided for the device input.
Safety instructions 4:

Further notes on operation

  • This device contains no parts that require maintenance. If an internal fuse trips, this is due to an internal defect.
  • The device is designed for areas with a degree of pollution 2 in controlled environments. No condensation or frost is allowed.
  • The device housing offers IP20 protection. The housing offers no protection against spilled liquids.
  • The device is designed to operate in areas between 5% and 95% relative humidity.
  • The device insulation is designed to withstand pulse voltages of overvoltage category III according to IEC 60664-1.
  • The device is suitable for supply from TN, TT or IT networks. The continuous voltage between the input terminal and the PE potential must not exceed 300 Vac.
  • The device is designed for altitudes up to 5000 m (16400 ft).
  • Above 2000 m a reduction in output current and over voltage category is required.