DC-OK function (parameterization)

The DC-OK function monitors the output voltage at the output terminals of an operating power supply via the process data.

1. Define the value for the DC OK threshold via the index 0x8000:16 "DC OK threshold"
Adjustment range 3.0 V to 30 V for nominal voltage UN = 24 V
Default: 22 V = 0.917 · UN
Hysteresis: typ. 0.5 V
If the output voltage (index 0x6000:11) falls below the DC OK threshold (index 0x8000:16), the DC OK bit (index 0x6000:04) is set to FALSE. In addition, the warning bit (index 0x6000:01) is also set to TRUE (see chapter "Setting the warning thresholds for the warning bit".