PS2001-2410-0000 | Power supply 24V, 10A, 1 phase, Extra Power
|
• AC 100-240V wide-range input • Efficiency of up to 95.2% • Excellent part-load efficiency • 120% peak power, 288W • Safe hiccup overload mode • Precise triggering of fuses through high overload / peak current • Active Power Factor Correction (PFC) • Minimum inrush current surge • Full output between -25°C and +60°C • DC-OK relay contact |
The power supply PS2001-2410-0000 is a single-phase, 24 V DC power supply with an output current of 10 A and an output power of 240 W.
On the input side, the device features a wide-range input, Active Power Factor Correction (PFC) and inrush current limiting.
The output operates according to the UI characteristic curve and switches to the safe hiccup mode in case of overload/short-circuit. The PS2001-2410-0000 features extra power with a continuous maximum output power of 120% and can precisely trigger fuses with a short peak current.
The power supply unit is part of the PS2000 family and has a width of 39 mm. A DC-OK LED and a potential-free relay contact monitor the status of the output voltage. Thanks to approvals for the process industry (ATEX/IECEx), shipbuilding (DNV) and the semiconductor industry (SEMI-F47), the power supply unit can be used in a wide range of applications.
Overview of technical data *)
Overview of technical data | PS2001-2410-0000 |
|---|---|
Output voltage | DC 24V (nominal factory setting 24.1V) |
Adjustment range | 24 - 28V |
Output current | 12.0-10.3A (amb. below +45°C) |
Input voltage AC | AC 100-240V -15%/+10% |
Mains frequency | 50-60Hz ±6% |
Input current AC | 2.15 / 1.13A at 120 / 230Vac |
Input voltage DC | DC 110-150V ±20% |
Efficiency | 93.6 / 95.2% at 120 / 230Vac |
Temperature range | -25°C to +70°C |
Size (W x H x D) | 39 x 124 x 117mm (without DIN rail) |
Weight | 600 g |
Approvals/markings | CE, EAC, UKCA |
*) All values typical for 24V, 10A, 230Vac, 50Hz, +25°C ambient temperature and after a warm-up period of five minutes, unless otherwise stated. |