Lifetime expectancy
The lifetime expectancy shown in the table indicates the minimum number of operating hours (service life) and is determined by the lifetime expectancy of the built-in electrolytic capacitors. The lifetime expectancy is stated in operating hours and is calculated according to the specifications of the capacitor manufacturer. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years (131,400h). Any number exceeding this value represents a calculated theoretical lifetime which can be used to compare devices.
| AC 100V | AC 120V | AC 230V |
|
|---|---|---|---|---|
Lifetime expectancy | 265,000h | 270,000h | 274,000h | At 24V, 2.5A and +40°C |
748,000h | 764,000h | 775,000h | At 24V, 2.5A and +25°C | |
128,000h | 143,000h | 166,000h | At 24V, 5A and +40°C | |
363,000h | 405,000h | 469,000h | At 24V, 5A and +25°C | |
81,000h | 96,000h | 119,000h | At 24V, 6A and +40°C | |
228,000h | 271,000h | 336,000h | At 24V, 6A and +25°C |