Operation on two phases
The power supply can also be used on two phases of a three-phase system. Such a phase-to-phase connection is permissible as long as the supply voltage is below 240V+10%.
Fig.25: Operation on two phasesMake sure that the connection cable connected to the N terminal is fused appropriately.
The maximum permissible voltage between one phase and the PE must be below 300Vac.