Hold-up time

The hold-up time is the time during which the output voltage of a power supply unit remains within the specification after a loss of input power. The hold-up time depends on the output load. Without load the hold-up time can be several seconds. The green DC-OK LED also lights up during this time.

 

 

230 Vac

 

Mains failure

Hold-up time

Typ.

69 ms

At 24 V, 2.5 A, see Fig. Hold-up time over input voltage

Min.

61 ms

At 24 V, 2.5 A, see Fig. Hold-up time over input voltage

Typ.

33 ms

At 24 V, 5 A, see Fig. Hold-up time over input voltage

Min.

29 ms

At 24 V, 5 A, see Fig. Hold-up time over input voltage

Hold-up time 1:Fig.5: Hold-up time over input voltage; switch-off behavior, definitions