Overview
PS1021-2405-0000 | Power supply 24V, 5A, single phase
|
• AC 100-120V / 200-240V input with automatic selection • Width only 39mm • Efficiency of up to 92.3% • Full power between -10°C and +55°C • Including DC-OK relay contact |
The PS1021-2405-0000 is a 1-phase 24 V power supply with an output current of 5 A and an output power of 120 W.
On the input side, the device has a wide-range input and an input inrush current limitation.
The output operates according to the UI characteristic curve and switches to the safe hiccup mode in case of overload/short-circuit.
The power supply is part of the PS1000 family and has a width of 39 mm. A DC OK LED and a potential-free relay contact monitor the status of the output voltage.
Overview of technical data *)
Overview of technical data | PS1021-2405-0000 |
|---|---|
Output voltage | DC 24V |
Adjustment range | 24 - 28V |
Output current | for AC 110-120 / 220-240V mains: for AC 100 / 200V mains: |
Output ripple | < 100mVpp, 20Hz to 20MHz |
Input voltage AC | AC 100-120 V / 220-240V (±10%, auto select) |
Mains frequency | 50-60Hz ±6% |
Input current AC | 1.72 / 1.05A at 120 / 230Vac |
Power factor | 0.64 / 0.54 at 120 / 230 Vac |
Efficiency | 91.2% / 92.3% at 120 / 230Vac |
Temperature range | -10°C to +70°C (in operation) |
Dimensions (W x H x D) | 39 x 124 x 124 mm |
Weight | 370 g |
Approvals/markings | CE, EAC, UKCA |
*) All values typical for 24V, 5A, 230Vac, 50Hz, +25°C ambient temperature and after a warm-up time of five minutes, unless otherwise stated.