EMC

The power supply is suitable for application in industrial environments as well as in residential, commercial and light industrial areas and small businesses.

EMC interference immunity

 

Strong transients

VDE 0160

Over the entire load range

750V, 0.3ms

EMC interference emission

According to generic standards: EN 61000-6-4

Conducted interference emission, input lines

EN 55011, EN 55015, EN 55022, FCC Part 15, CISPR 11, CISPR 22

Class B

Conducted interference emission, output lines 1)

IEC/CISPR 16-1-2, IEC/CISPR 16-2-1

Limit values for the DC power connection according to EN 61000-6-3 not met

Interference emission

EN 55011, EN 55022

Class B

Harmonic input current

EN 61000-3-2

Met, class A limits

Voltage fluctuations, flicker

EN 61000-3-3

Met, tested with non-pulsating constant current loads.

This device complies with FCC Part 15.

Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must be able to deal with any interference received, including interference that may cause undesired operation.

1) for information only, not mandatory for EN 61000-6-3

Switching frequencies

PFC converter

60kHz to 140kHz

Input load and output voltage dependent

Main converter

65kHz to 150kHz

Output voltage and output load dependent