Terminals and wiring
The terminals are designed to be finger-safe according to IP20 and are suitable for field or factory wiring.
Technical data | Input | Output | DC-OK signal |
|---|---|---|---|
Connection cross-section | e*: max. 6mm² f*: max. 4mm² a*: max. 4mm² (d<2.8mm) | e*: max. 6mm² f*: max. 4mm² a*: max 4mm² (d<2.8mm) | e*: max. 1.5mm² f*: max. 1.5mm² a*: max. 1.5mm² (d<1.6mm) |
Connection cross section (AWG) | e*: AWG 20-10 f*: AWG 20-10 a* AWG 20-10 (d<2.8mm) | e*: AWG 20-10 f*: AWG 20-10 a* AWG 20-10 (d<2.8mm) | e*: AWG 28-16 f*: AWG 28-16 a*: AWG 28-16 (d<1.6 mm) |
Strip length | 7mm / 0.28inch | 7mm / 0.28inch | 7mm / 0.28inch |
e* = solid wire
f* = stranded wire
a* = with ferrule
Instructions
- Use suitable copper cables that are designed for a minimum operating temperature of:
- 75°C for ambient temperatures up to 55°C and
- 90°C for ambient temperatures up to at least 70°C. - Observe national installation rules and regulations!
- Make sure all individual wires of a strand enter the terminal connection!
- Do not use the device without PE connection.
- Unused terminal spaces should be tightened securely.
- Ferrules are permissible.