80EF:1A Peak Current Error Threshold
Peak current limit in ampere of the fuse, to protect the fuse. If the actual current is greater than the "Peak Current Error Threshold", the module will intervene and open the relay. The diagnosis "Fuse Utilization Error"(6pp1:07) will be set to true.
|
Description |
Value |
|---|---|
|
Index |
0x80EF (Device) |
|
Subindex |
0x1A |
|
Datatype |
REAL32 |
|
Min. Value |
0.0 |
|
Default |
20.0 |
|
Max. Value |
100.0 |
|
Unit |
A |
|
Access / EtherCAT-State |
Rw |
|
PDO Mapping |
|
|
Revision |
All |