80DF:19 Fuse Utilization Current Time Constant
i²t time constant in seconds of the fuse, to protect the fuse. If the measured i²t is greater than the "Fuse Utilization Current Threshold"(8ppF:07), the module will intervene and open the relay. The diagnosis "Fuse Utilization Error"(6pp1:07) will be set to true.
|
Description |
Value |
|---|---|
|
Index |
0x80DF (Device) |
|
Subindex |
0x19 |
|
Datatype |
REAL32 |
|
Min. Value |
0.0 |
|
Default |
20.0 |
|
Max. Value |
100.0 |
|
Unit |
s |
|
Access / EtherCAT-State |
Rw |
|
PDO Mapping |
|
|
Revision |
All |