Adding the PROFINET master
The PROFINET master is added in the TwinCAT System Manager in the same way as the PROFINET slave. You can then find all connected slaves via the master. The following section illustrates how to add a PROFINET master in TwinCAT.
Prerequisites for this step:
- TwinCAT must be in Config mode.
- A selected target system (in this sample it is the Embedded PC CX5020-M930)
Add a PROFINET master as follows:
- 1. In the tree view on the left, right-click on Devices.
- 2. In the context menu click on Scan.

- 3. Select the devices you want to use and confirm the selection with OK.

- 4. Confirm the request with Yes, in order to look for boxes.
The Scan Devices window appears. - 5. Select the PROFINET slaves you want to use and click Add Devices.

- The selected PROFINET slaves are then displayed on the left in the tree view. The PROFINET slaves are assigned IP addresses based on the PROFINET master.

If you do not find all PROFINET slaves, check the wiring and search for the PROFINET slaves again.