Process input data (DataIN)

Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Channel

Ch4

Ch3

Ch2

Ch1

Name

curr

IN3

IN2

IN1

curr

IN3

IN2

IN1

curr

IN3

IN2

IN1

curr

IN3

IN2

IN1

Key

Bit

Channel/Name

Description

15

Ch4 curr

0bin

Current is lower than the switching threshold specified for channel 4

1bin

Current is higher than the switching threshold specified for channel 4

14

Ch4 IN3

Channel 4, input 3

13

Ch4 IN2

Channel 4, input 2

12

Ch4 IN1

Channel 4, input 1

11

Ch3 curr

0bin

Current is lower than the switching threshold specified for channel 3

1bin

Current is higher than the switching threshold specified for channel 3

10

Ch3 IN3

Channel 3, input 3

9

Ch3 IN2

Channel 3, input 2

8

Ch3 IN1

Channel 3, input 1

7

Ch2 curr

0bin

Current is lower than the switching threshold specified for channel 2

1bin

Current is higher than the switching threshold specified for channel 2

6

Ch2 IN3

Channel 2, input 3

5

Ch2 IN2

Channel 2, input 2

4

Ch2 IN1

Channel 2, input 1

3

Ch1 curr

0bin

Current is lower than the switching threshold specified for channel 1

1bin

Current is higher than the switching threshold specified for channel 1

2

Ch1 IN3

Channel 1, input 3

1

Ch1 IN2

Channel 1, input 2

0

Ch1 IN1

Channel 1, input 1