Settings
Settings for parameterizing the KM2774-0000.

Current limit
Channel 1 (R34)
Here you can set the current limit for channel 1 (default: 1500 mA).
Permissible value range: 50 to 1500 mA.
Channel 2 (R35)
Here you can set the current limit for channel 1 (default: 1500 mA).
Permissible value range: 50 to 1500 mA.
Channel 3 (R36)
Here you can set the current limit for channel 1 (default: 1500 mA).
Permissible value range: 50 to 1500 mA.
Channel 4 (R37)
Here you can set the current limit for channel 1 (default: 1500 mA).
Permissible value range: 50 to 1500 mA.
Dead time
Dead time for channel 1 (R38)
Here you can define the dead time until overcurrent shutdown for channel 1 (default: 400 ms).
Permissible value range: 100 to 2560 ms in steps of 10 ms.
If you enter 0 ms, the dead time is disabled. The output switches off immediately when the current limit is exceeded.
Dead time for channel 2 (R39)
Here you can define the dead time until overcurrent shutdown for channel 2 (default: 400 ms).
Permissible value range: 100 to 2560 ms in steps of 10 ms.
If you enter 0 ms, the dead time is disabled. The output switches off immediately when the current limit is exceeded.
Dead time for channel 3 (R40)
Here you can define the dead time until overcurrent shutdown for channel 3 (default: 400 ms).
Permissible value range: 100 to 2560 ms in steps of 10 ms.
If you enter 0 ms, the dead time is disabled. The output switches off immediately when the current limit is exceeded.
Dead time for channel 4 (R41)
Here you can define the dead time until overcurrent shutdown for channel 4 (default: 400 ms).
Permissible value range: 100 to 2560 ms in steps of 10 ms.
If you enter 0 ms, the dead time is disabled. The output switches off immediately when the current limit is exceeded.