Technical data

Technical data

KM2004

Number of outputs

32 (4 x 8)

Nominal voltage

24 VDC (-15%/+20%)

Load type

ohmic, inductive, lamp load

Output current per channel

max. 0.5 A

Short circuit current

0.6 ... 1.0 A

Breaking energy (inductive)

< 150 mJ/channel

Power supply for the electronics

via the K-Bus

Current consumption from K-bus

typically 5 mA

Current consumption from the load voltage (24 V)

typically 15 mA

With of a bus terminal block

max. 64 standard bus terminals or 80 cm
(for this a KM2004 is equivalent to 4 standard bus terminals)

Electrical isolation

500 V (K-Bus / signal voltage)

Bit width in the output process image

32 bit

Dimensions with connector (W x H x D)

approx. 75mm x 100 mm x 55mm (aligned width: 73mm), see dimensional drawing

Weight (without connector)

approx. 150 g

Permissible ambient temperature range during operation

0°C...+55°C

Permissible ambient temperature range during storage

-25°C...+85°C

Permissible relative humidity

95%, no condensation

Mounting

on 35 mm mounting rail according to EN 60715, see Recommended mounting rails

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC resistance burst / ESD

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP20

Installation position

variable

Approvals / markings*

CE, UKCA, EAC

*) Real applicable approvals/markings see type plate on the side (product marking).