Connection

X1: Signal connection, digital outputs, D-Sub 25

The KM2042 digital output module transmits the binary control signals from the automation device on to the actuators at the process level.

The 16 outputs deliver load currents of up to 0.5 A, although the total current from all the outputs must not exceed 4 A.

The signal connection is made through a 25-pin D-Sub socket.

The outputs are short-circuit proof and protected against inverse connection.

Connection 1:
Assignment of the 25-pin D-sub socket

X2: Connection of the voltage supply for the outputs

Name

Description

24 V

Supply voltage 24 V

0 V

Supply voltage 0 V

Block diagram

Connection 2:
Block diagram