Technical data

Technical data

KM1008

KM1018

Number of inputs

64 (8 x 8)

Rated voltage

24 VDC (-15%/+20%)

Signal voltage “0”

-3 V ... 5 V

Signal voltage “1”

15 V ... 30 V

Input filter

3.0 ms

0.2 ms

Input current

typically 5 mA

Power supply for the electronics

via the K-Bus

Current consumption from K-bus

typically 3 mA

Width of a bus terminal block

Maximum 64 standard Bus Terminals or 80 cm
(one KM10x8 corresponds to 8 standard Bus Terminals here)

Electrical isolation

500 V (K-Bus / signal voltage)

Bit width in the input process image

64 bit

Dimensions with connectors (w x h x d)

approx. 123mm x 100mm x 55mm (width aligned: 121mm), see dimensional drawing

Weight (without connectors)

approx. 225 g

Permissible ambient temperature range during operation

0°C ... +55°C

Permissible ambient temperature range during storage

-25°C ... +85°C

Permissible relative humidity

95%, no condensation

Mounting

on 35 mm mounting rail conforms to EN 60715, see Recommended mounting rails

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC immunity / emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP20

Installation position

variable

Approvals / markings*

CE, UKCA, EAC

*) Real applicable approvals/markings see type plate on the side (product marking).