KL9570 - Buffer Capacitor Terminal

ATEX - Special conditions (standard temperature range)

 
WARNING
Observe the special conditions for the intended use of Beckhoff fieldbus components with standard temperature range in potentially explosive areas (directive 94/9/EU)!
•
The certified components are to be installed in a suitable housing that guarantees a protection class of at least IP54 in accordance with EN 60529! The environmental conditions during use are thereby to be taken into account!
•
If the temperatures during rated operation are higher than 70°C at the feed-in points of cables, lines or pipes, or higher than 80°C at the wire branching points, then cables must be selected whose temperature data correspond to the actual measured temperature values!
•
Observe the permissible ambient temperature range of 0 to 55°C for the use of Beckhoff fieldbus components standard temperature range in potentially explosive areas!
•
Measures must be taken to protect against the rated operating voltage being exceeded by more than 40% due to short-term interference voltages!
•
The individual terminals may only be unplugged or removed from the Bus Terminal system if the supply voltage has been switched off or if a non-explosive atmosphere is ensured!
•
The connections of the certified components may only be connected or disconnected if the supply voltage has been switched off or if a non-explosive atmosphere is ensured!
•
The fuses of the KL92xx/EL92xx power feed terminals may only be exchanged if the supply voltage has been switched off or if a non-explosive atmosphere is ensured!
•
Address selectors and ID switches may only be adjusted if the supply voltage has been switched off or if a non-explosive atmosphere is ensured!
 

Standards

The fundamental health and safety requirements are fulfilled by compliance with the following standards:

▪
EN 60079-0:2012+A11:2013
▪
EN 60079-15:2010
 
 

Marking

The Beckhoff fieldbus components with standard temperature range certified for potentially explosive areas bear one of the following markings:

 ex-logo_120x94II 3G   KEMA 10ATEX0075 X Ex nA IIC T4 Gc   Ta: 0 … 55°C

or

 ex-logo_120x94II 3G   KEMA 10ATEX0075 X Ex nC IIC T4 Gc   Ta: 0 … 55°C