Error codes

Value (hex)

Value (dec)

Description

0x0000

0

No error

0x8001

32769

Watchdog Error. The terminal does not respond. This message usually means that there is no connection to the terminal.

  • Is the terminal linked to the variables in the TwinCAT System Manager?
  • Terminal plugged in incorrectly?
  • Clean all, rebuild all and load again into the TwinCAT System Manager?

0x8002

32770

Incorrect terminal connected. The terminal type can be checked in online mode (uiTerm - internal variable of the function block).

0x8003

32771

The input variable wOut of the function block FB_KL8548() is too big. Maximum 32767 is allowed. Processing continues internally (in the function block) with 32767 (corresponds to 10 V).

0x8004

32772

The function block FB_KL8524() tries to set the outputs 1 and 2 simultaneously on channel 1. That is not allowed. No output is set.

0x8005

32773

The function block FB_KL8524() tries to set the outputs 1 and 2 simultaneously on channel 2. That is not allowed. No output is set.

0x8006

32774

The function block FB_KL8524() tries to set the outputs 1 and 2 simultaneously on channel 3. That is not allowed. No output is set.

0x8007

32775

The function block FB_KL8524() tries to set the outputs 1 and 2 simultaneously on channel 4. That is not allowed. No output is set.