KL8548 - Process image

The KL8548 is represented in the process image with 24 bytes each of input and output data. These are organized as follows:

Byte offset
(without word alignment)

Byte offset
(with word alignment*)

Format

Input data

Output data

0

0

Byte

SB1

CB1

1

2

Word

DataIN1

DataOUT1

3

4

Byte

SB2

CB2

4

6

Word

DataIN2

DataOUT2

6

8

Byte

SB3

CB3

7

10

Word

DataIN3

DataOUT3

9

12

Byte

SB4

CB5

10

14

Word

DataIN4

DataOUT4

12

16

Byte

SB1

CB1

13

18

Word

DataIN5

DataOUT5

15

20

Byte

SB2

CB2

16

22

Word

DataIN6

DataOUT6

18

24

Byte

SB3

CB3

19

26

Word

DataIN7

DataOUT7

21

28

Byte

SB4

CB5

22

30

Word

DataIN8

DataOUT8

*) Word alignment: The Bus Coupler places values on even byte addresses

Key

SB1 to SB8: status bytes of channels 1 to 8
CB1 to CB8: control bytes of channels 1 to 8
DataIN1 to DataIN8: input words of channels 1 to 8
DataOUT1 to DataOUT8: output words of channels 1 to 8

Control and status byte

See chapter Control and status byte

Process data

Input data (DataIN1 to DataIN8)

Position of the potentiometers with user scaling switched off (R32.0 = 0)

Potentiometer
position

Input value in the PLC

hexadecimal

decimal

CCW stop

0x0000

0

Center

0x3FFF

16383

CW stop

0x7FFF

32767

Output data (DataOUT1 to DataOUT8)

Specification of the output values by the controller.

Output value

Output voltage

hexadecimal

decimal

0x0000

0

0 V

0x3FFF

16383

+5 V

0x7FFF

32767

+10 V