Parameter registers (overview)

These registers are used to parameterize the power terminal. They can be read or written by means of register communication.

Parameter registers (overview) 1:

Transferring new values after a power-off reset

Carry out a power-off reset (switching the terminal off and then on again) each time the terminal registers are changed so that the new values are also adopted by the measurement unit!

PR no.

Comment

Default value

R/W

Memory

PR0

reserved

-

-

-

-

...

...

...

...

...

...

PR5

reserved

-

-

-

-

PR6

Diagnostic register

-

-

R

RAM

PR7

Command register

0x0000

0dec

-

-

PR8

Terminal type

0x1F41

8001dec

R

ROM

PR9

Firmware version

e.g. 0x3141

12609dec

R

ROM

PR10

Multiplex shift register

0x0230 / 0x0418

560dec / 1048dec

R

ROM

PR11

Signal channels

0x0160

352dec

R

ROM

PR12

Minimum data length

0x6060

24672dec

R

ROM

PR13

Data structure

0x0007

7dec

R

ROM

PR14

reserved

-

-

-

-

PR1

Alignment register

-

-

R/W

RAM

PR16

Hardware Version

e.g. 0x0000

e.g. 0dec

R/W

Flash

PR17

L1 voltage gain compensation

e.g. 0x0B00

e.g. 2816dec

R/W

Flash

PR18

L2 voltage gain compensation

e.g. 0x0B00

e.g. 2816dec

R/W

Flash

PR19

L3 voltage gain compensation

e.g. 0x0B00

e.g. 2816dec

R/W

Flash

PR20

L1 current gain compensation

e.g. 0x3000

e.g. 12288dec

R/W

Flash

PR21

L2 compensation gain current

e.g. 0x3000

e.g. 12288dec

R/W

Flash

PR22

L3 compensation gain current

e.g. 0x3000

e.g. 12288dec

R/W

Flash

PR23

Hall Sensor Sensitivity

0x1FE3

8163dec

R/W

Flash

PR24

reserved

-

-

-

-

...

...

...

...

...

...

PR30

reserved

-

-

-

-

PR31

Code word register

-

-

R/W

RAM

PR32

Feature-Register

0x0221

545dec

R/W

Flash

PR33

Rated current L1

0x0000

0dec

R/W

Flash

PR34

Switch-on threshold L1

0x0000

0dec

R/W

Flash

PR35

Overvoltage threshold L1

0x0DAC

3500dec

R/W

Flash

PR36

Undervoltage threshold L1

0x0096

150dec

R/W

Flash

PR37

Overload threshold L1

0x09C4

2500dec

R/W

Flash

PR38

Underload threshold L1

0x0000

0dec

R/W

Flash

PR39

Rated current L2

0x0000

0dec

R/W

Flash

PR40

Switch-on threshold L2

0x0000

0dec

R/W

Flash

PR41

Overvoltage threshold L2

0x0DAC

3500dec

R/W

Flash

PR42

Undervoltage threshold L2

0x0096

150dec

R/W

Flash

PR43

Overload threshold L2

0x09C4

2500dec

R/W

Flash

PR44

Underload threshold L2

0x0000

0dec

R/W

Flash

PR45

Rated current L3

0x0000

0dec

R/W

Flash

PR46

Switch-on threshold L3

0x0000

0dec

R/W

Flash

PR47

Overvoltage threshold L3

0x0DAC

3500dec

R/W

Flash

PR48

Undervoltage threshold L3

0x0096

150dec

R/W

Flash

PR49

Overload threshold L3

0x09C4

2500dec

R/W

Flash

PR50

Underload threshold L3

0x0000

0dec

R/W

Flash

PR51

Maximum current difference

0x01F4

500dec

R/W

Flash

PR52

Tripping class

0x000A

10dec

R/W

Flash

PR53

Measuring cycle time

0x0032

50dec

R/W

Flash

PR54

reserved

-

-

-

-

...

...

...

...

...

...

PR63

reserved

-

-

-

-