Scenes
Fig.33: KS2000 - archive - scenesHere you specify the light values for up to 16 scenes (listed horizontally) for up to 64 DALI devices (listed vertically).
The following entries are valid:
- 0 to 254: light values (0: off, 254: maximum brightness)
- 255: Mask (on changing to the new scene, the device retains its existing value).
In the example shown, for
- DALI device 1 the light value 50 is assigned for scene 3, the light value 100 for scene 5, and the light value 250 for scene 10;
- DALI device 8 the light value 200 is assigned for scene 4, the light value 150 for scene 6, and the light value 20 for scene 12;
- DALI device 18 the light value 254 is assigned for scenes 3, 4, 5, 6, 10 and 12.
Visual selection feedback
If the option visual selection feedback is enabled and you click in the scene column, all DALI devices for this scene are assigned the light values entered in this column.
This also requires Online Monitoring to be enabled under Options in the KS2000, and the I/O Run LED on the Bus Coupler must be on.