Addressing the DALI devices

Physical selection

Addressing the DALI devices 1:Fig.24: KS2000 - addressing of the DALI device - physical selection
Addressing the DALI devices 2:

Do not interrupt the addressing process

The addressing procedure must not be interrupted by other DALI commands. Make sure of this by, for instance, interrupting your PLC program or the K-Bus cycle before starting the addressing.

Sequence of actions for physical addressing

1. Click the Start button in order to begin the addressing procedure.
Addressing the DALI devices 3:

Addresses

If you have selected Complete new installation, all previous addresses will be deleted. Otherwise you can add further devices to the existing addressing scheme. If you have not selected Delete all group assignments, the assignment of addresses to groups is retained. Bear this in mind when reassign in the addresses!

2. The following instruction now appears in the status line:
Wait for a device to be selected. Remove the lamp!
3. After the lamp has been removed, the instruction that appears in the status line is as follows:
The device was addressed. Add the lamp again!
After reinserting the lamp, it flashes three times in order to indicate that the address assignment has been successful.
The newly addressed device is now shown in the list of short addresses.
4. Repeat Point 2 and Point 3 for every DALI device that is to be re-addressed.
5. When you have assigned all the addresses, complete the addressing procedure by clicking the Cancel button.

The newly addressed devices will be shown in the list of short addresses:

Addressing the DALI devices 4:Fig.25: KS2000 - addressing of the DALI device - displaying the physical addressing

Random addressing

With this method, addresses are assigned randomly.

Addressing the DALI devices 5:Fig.26: KS2000 - addressing of the DALI device - random addressing

The operator has no influence on the order of the address assignment. The order can, however, be modified retrospectively via the Modify addresses tab.

Addressing the DALI devices 6:Fig.27: KS2000 - addressing the DALI devices - displaying the randomly assigned addresses

Single assignment

With this method, all DALI devices connected to the KL6811 are assigned the same new address. In practice, only the one DALI device, which is to be assigned this address, will therefore be connected, before the Start button is pressed.

Addressing the DALI devices 7:Fig.28: KS2000 - addressing of the DALI devices - single assignment

Modify addresses

In the list on the right select the device, whose address you want to change. Via the New Address selection box you can select a new address for the selected device.

Once you have selected all new addresses, click on Start to allocate the addresses to the devices.

Addressing the DALI devices 8:Fig.29: KS2000 - addressing of the DALI devices - Modify addresses

Visual selection feedback

If the option visual selection feedback is enabled, the selected device (in the example device #04) sets its current lamp power value to the parameterized maximum value.