KL6583 - Technical Data
Technical data | KL6583 | KL6583-0100** |
|---|---|---|
Connection | 2 x 2-wire directly at the KL6581 Bus Terminal | |
Transmission standard | CAN | |
CAN connection cable | Beckhoff ZB5100 (sold by the meter) | |
Permitted cable length from the KL6581 to the last KL6583 | maximum 500 m (line topology only) | |
Data transfer rate | 125 kbyte | |
Electrical isolation | none | |
Power supply for the electronics | from the power contacts of the KL6581 (24 VDC) | |
Current consumption from the power contacts of the KL6581 | typical 20 mA (24 VDC) | |
Center frequency | 868.3 mHz | 315 MHz |
Occupied frequency band | 868.0 … 868.6 MHz (600 kHz) | - |
Maximum transmission power (permissible) | 25 mW e.r.p. | - |
Transmission power | 2 mW (3 dBm) | - |
Receiver category | 2 | - |
Transfer range | 300 m in free field, | |
Radio telegram | depending on sensor type (32-bit sensor ID number, number of user bytes unlimited), sending and receiving | |
Antenna | integrated in the housing | |
Weight | approx. 90 g | |
Housing | round upper section for installation (ceiling/wall) with flange connection for main housing, upper section with cable opening; color: grey-white (RAL 9002) | |
Dimensions | Height: 57 mm, | |
Mounting | variable | |
Permissible ambient temperature range during operation | 0 °C ... + 55 °C | |
Permissible ambient temperature range during storage | -25 °C ... + 85 °C | |
Permissible relative air humidity | 95 %, no condensation | |
Vibration / shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27 | |
EMC immunity / emission | conforms to EN 61000-6-2 / EN 61000-6-4 | |
Protection class | IP40 | |
Installation position | variable | |
Approvals/markings* | CE | FCC |
Permission for operation in | European Union | USA and Canada |
*) Real applicable approvals/markings see type plate on the side (product marking).
**) The KL6583-0100 EnOcean transceiver is no longer available.
Supported EnOcean telegrams
Telegram | RORG | ORG | Communication |
|---|---|---|---|
RPS | F6 | 05 | Repeated Switch Communication |
1BS | D5 | 06 | 1 Byte Communication |
4BS | A5 | 07 | 4 Byte Communication |