KL6581 - Technical data
Technical data | KL6581 |
|---|---|
Technology | EnOcean |
Number of channels | 1 |
Number of connectable KL6583s | 8 |
Transmission standard | CAN |
CAN connection cable | Beckhoff ZB5100 (sold by the meter) |
Permitted cable length from the KL6581 to the last KL6583 | maximum 500 m (line topology only) |
Data transfer rate | 125 kbyte |
Electrical isolation | 500 V (K-bus/CAN) |
Power supply for the electronics | via the K-bus and through the power contacts |
Current consumption from K-bus | typically 60 mA |
Bit width in process image | Output: 12 bytes data, input: 12 bytes data |
Weight | approx. 85 g |
Dimensions (W x H x D) | approx. 15mm x 100mm x 70mm |
on 35 mm mounting rail conforms to EN 60715 | |
Permissible ambient temperature range during operation | 0 °C ... + 55 °C |
Permissible ambient temperature range during storage | -25 °C ... + 85 °C |
Permissible relative air humidity | 95 %, no condensation |
Vibration / shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27 |
EMC immunity / emission | conforms to EN 61000-6-2 / EN 61000-6-4 |
Protection class | IP20 |
Installation position | variable |
Approvals/markings* | CE, cULus, EAC |
*) Real applicable approvals/markings see type plate on the side (product marking).
Supported EnOcean telegrams
Telegram | RORG | ORG | Communication |
|---|---|---|---|
RPS | F6 | 05 | Repeated Switch Communication |
1BS | D5 | 06 | 1 Byte Communication |
4BS | A5 | 07 | 4 Byte Communication |