KL9520 - AS-i potential feed terminal with filter

KL9520 - AS-i potential feed terminal with filter 1:Fig.5: KL9520 - AS-i potential feed terminal with filter

The KL9520 enables AS-i networks to be supplied from standard power supply units or another AS-Interface network. The combination of KL9520 and AS-i master terminal can be repeated several times in a Bus Terminal block, thereby saving several AS-i power supply units.

The KL9520 potential feed terminal decouples the input and output voltage through an integrated filter. There is no short-circuit protection and no electrical isolation between the input voltage and the output voltage!

The connection to the KL6211 AS-i master terminal is established by the power contacts during side-by-side plugging.
The KL6201 AS-i master terminal must be connected via cable bridges.

LED display

LED

Meaning

Power (green)

off

AS-i voltage is switched off.

on

AS-i voltage is switched on.

Technical data

Technical data

KL9520 / KS9520

Input voltage

up to 35 VDC

Output voltage

up to 35 VDC

Input current

max. 2 A

Output current

max. 2 A (not short-circuit-proof)

Current consumption from K-bus

0 mA

Isolation
voltage

AS-i / K-bus

1500 VAC (permanently)

input / output voltage

none

Configuration

no address or configuration settings required

Bit width in process image

0 input bits, 0 output bits

Weight

app. 90 g

Permissible ambient temperature during operation

0°C ... +55°C

Permissible ambient temperature during storage

-25°C ... +85°C

Permissible relative humidity

95 %, no condensation

Pluggable wiring

for all KSxxxx Bus Terminals

Mounting

on 35 mm mounting rail conforms to EN 60715

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

Enhanced mechanical load capacity

yes, see installation instructions for enhanced mechanical load capacity

EMC resistance burst / ESD

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP20

Installation position

variable

Approvals / markings*

CE, UKCA, EAC

*) Real applicable approvals/markings see type plate on the side (product marking).