Example 2: Writing to an user register
![]() | Code word In normal mode all user registers are read-only with the exception of Register 31. In order to deactivate this write protection you must write the code word (0x1235) into Register 31. If a value other than 0x1235 is written into Register 31, write protection is reactivated. Please note that changes to a register only become effective after restarting the terminal (power-off/power-on). |
I. Write the code word (0x1235) into register 31.
Output Data
Byte 0: Control byte | Byte 1: DataOUT1, high byte | Byte 2: DataOUT1, low byte |
---|---|---|
0xDF (1101 1111bin) | 0x12 | 0x35 |
Explanation:
- Bit 0.7 set means: Register communication switched on.
- Bit 0.6 set means: writing to the register.
- Bits 0.5 to 0.0 specify the register number 31 with 01 1111bin.
- The output data word (byte 1 and byte 2) contains the code word (0x1235) for deactivating write protection.
Input Data (answer of the Bus Terminal)
Byte 0: Status byte | Byte 1: DataIN1, high byte | Byte 2: DataIN1, low byte |
---|---|---|
0x9F (1001 1111bin) | 0xXX | 0xXX |
Explanation:
- The terminal returns a value as a receipt in the status byte that differs only in bit 0.6 from the value of the control byte.
- The input data word (byte 1 and byte 2) is of no importance after the write access. Any values still displayed are invalid!
II. Read Register 31 (check the set code word)
Output Data
Byte 0: Control byte | Byte 1: DataOUT1, high byte | Byte 2: DataOUT1, low byte |
---|---|---|
0x9F (1001 1111bin) | 0xXX | 0xXX |
Explanation:
- Bit 0.7 set means: Register communication switched on.
- Bit 0.6 not set means: reading the register.
- Bits 0.5 to 0.0 specify the register number 31 with 01 1111bin.
- The output data word (byte 1 and byte 2) has no meaning during read access.
Input Data (answer of the Bus Terminal)
Byte 0: Status byte | Byte 1: DataIN1, high byte | Byte 2: DataIN1, low byte |
---|---|---|
0x9F (1001 1111bin) | 0x12 | 0x35 |
Explanation:
- The terminal returns the value of the control byte as a receipt in the status byte.
- The terminal returns the current value of the code word register in the input data word (byte 1 and byte 2).
III. Write to Register 32 (change contents of the feature register)
Output data
Byte 0: Control byte | Byte 1: DataIN1, high byte | Byte 2: DataIN1, low byte |
---|---|---|
0xE0 (1110 0000bin) | 0x00 | 0x02 |
Explanation:
- Bit 0.7 set means: Register communication switched on.
- Bit 0.6 set means: writing to the register.
- Bits 0.5 to 0.0 indicate register number 32 with 10 0000bin.
- The output data word (byte 1 and byte 2) contains the new value for the feature register.
| |
Observe the register description! The value of 0x0002 given here is just an example! |
Input data (response from the Bus Terminal)
Byte 0: Status byte | Byte 1: DataIN1, high byte | Byte 2: DataIN1, low byte |
---|---|---|
0xA0 (1010 0000bin) | 0xXX | 0xXX |
Explanation:
- The terminal returns a value as a receipt in the status byte that differs only in bit 0.6 from the value of the control byte.
- The input data word (byte 1 and byte 2) is of no importance after the write access. Any values still displayed are invalid!
IV. Read register 32 (check changed feature register)
Output Data
Byte 0: Control byte | Byte 1: DataOUT1, high byte | Byte 2: DataOUT1, low byte |
---|---|---|
0xA0 (1010 0000bin) | 0xXX | 0xXX |
Explanation:
- Bit 0.7 set means: Register communication switched on.
- Bit 0.6 not set means: reading the register.
- Bits 0.5 to 0.0 indicate register number 32 with 10 0000bin.
- The output data word (byte 1 and byte 2) has no meaning during read access.
Input Data (answer of the Bus Terminal)
Byte 0: Status byte | Byte 1: DataIN1, high byte | Byte 2: DataIN1, low byte |
---|---|---|
0xA0 (1010 0000bin) | 0x00 | 0x02 |
Explanation:
- The terminal returns the value of the control byte as a receipt in the status byte.
- The terminal returns the current value of the feature register in the input data word (byte 1 and byte 2).
V. Write register 31 (reset code word)
Output Data
Byte 0: Control byte | Byte 1: DataOUT1, high byte | Byte 2: DataOUT1, low byte |
---|---|---|
0xDF (1101 1111bin) | 0x00 | 0x00 |
Explanation:
- Bit 0.7 set means: Register communication switched on.
- Bit 0.6 set means: writing to the register.
- Bits 0.5 to 0.0 specify the register number 31 with 01 1111bin.
- The output data word (byte 1 and byte 2) contains 0x0000 for reactivating write protection.
Input Data (answer of the Bus Terminal)
Byte 0: Status byte | Byte 1: DataIN1, high byte | Byte 2: DataIN1, low byte |
---|---|---|
0x9F (1001 1111bin) | 0xXX | 0xXX |
Explanation:
- The terminal returns a value as a receipt in the status byte that differs only in bit 0.6 from the value of the control byte.
- The input data word (byte 1 and byte 2) is of no importance after the write access. Any values still displayed are invalid!