Register overview
|
Register |
Comment |
Default value |
R/W |
Memory | ||
|---|---|---|---|---|---|---|
|
KL5151-0021: |
Filter register |
0x0000 |
0dec |
R/W |
RAM | |
|
other types: |
reserved |
- |
- |
- |
- | |
|
R1 to R5 |
reserved |
- |
- |
- |
- | |
|
R6 |
Diagnostic register (not used) |
0x0000 |
0dec |
R |
RAM | |
|
R7 |
Command register (not used) |
0x0000 |
0dec |
R/W |
RAM | |
|
Terminal description |
KL5151-0000: |
0x141F |
5151dec |
R |
ROM | |
|
KL5151-0023: | ||||||
|
KL5151-0050: | ||||||
|
KL5152-0000: |
0x1420 |
5152dec | ||||
|
Firmware version |
e.g. 0x3341 |
e.g. 3AASCII |
R |
ROM | ||
|
Multiplex shift register |
0x0228 |
552dec |
R |
ROM | ||
|
Signal channels |
KL5151-0000: |
0x0128 |
296dec |
R |
ROM | |
|
KL5151-0023: |
0x0150 |
336dec | ||||
|
KL5151-0050: |
0x0228 |
552dec | ||||
|
KL5152-0000: | ||||||
|
Minimum data length |
KL5151-0000: |
0x2828 |
10280dec |
R |
ROM | |
|
KL5151-0023: |
0x5050 |
20560dec | ||||
|
KL5151-0050: |
0xA8A8 |
43176dec | ||||
|
KL5152-0000: | ||||||
|
Data type |
0x0006 |
6dec |
R |
ROM | ||
|
R14 |
reserved |
- |
- |
- |
- | |
|
R15 |
Alignment register |
variable |
variable |
R/W |
RAM | |
|
Hardware version |
e.g. 0x0000 |
e.g. 0dec |
R/W |
SEEROM/RAM | ||
|
R17 to R30 |
reserved |
- |
- |
- |
- | |
|
Terminal type |
KL5151-0000: |
0x0000 |
0dec |
R |
ROM | |
|
KL5151-0023: |
0x0017 |
23dec | ||||
|
KL5151-0050: |
0x0032 |
50dec | ||||
|
KL5152-0000: |
0x0000 |
0dec | ||||
|
Code word register |
0x0000 |
0dec |
R/W |
RAM | ||
|
Feature register |
KL5151-0000: |
0x0000 |
0dec |
R/W |
SEEROM/RAM | |
|
KL5151-0023: |
0x0000 |
0dec | ||||
|
KL5151-0050: |
0x00C0 |
192dec | ||||
|
KL5152-0000: | ||||||
|
R33 to R34 |
reserved |
- |
- |
- |
- | |
|
KL5151-0021 |
Filter default |
0x0000 |
0dec |
R/W |
SEEROM/RAM | |
|
other types |
reserved |
- |
- |
- |
- | |
|
R36 to R63 |
reserved |
- |
- |
- |
- | |