Standard format

The KL5101 is mapped into the bus coupler depending on the set parameters. The terminal always occupies memory space in the process image of the inputs and outputs.

Conditions

Word offset

High Byte

Low Byte

Complete evaluation: any

Motorola format: no

Word alignment: no

0

D0

CB/SB

1

D2

D1

2

D4

D3

Conditions

Word offset

High Byte

Low Byte

Complete evaluation: any

Motorola format: yes

Word alignment: no

0

D1

CB/SB

1

D2

D0

2

D3

D4

Conditions

Word offset

High Byte

Low Byte

Complete evaluation: any

Motorola format: no

Word alignment: yes

0

-

CB/SB

1

D1

D0

2

-

D2

3

D4

D3

Conditions

Word offset

High Byte

Low Byte

Complete evaluation: any

Motorola format: yes

Word alignment: yes

0

-

CB/SB

1

D0

D1

2

-

D2

3

D3

D4

Complete evaluation

The terminal is mapped with control and status byte.

Motorola format

Motorola or Intel format can be set.

Word alignment

The terminal is positioned on a word limit in the Bus Coupler.

CB

Control byte (appears in the process image of the outputs).

SB

Status byte (appears in the process image of the inputs).

D0/D1

Counter word (read/set)

(D2)

The period duration is output here, together with D3/D4.

D3/D4

Latch word (read)

“-“

This byte is not used or occupied by the terminal.