Control and status bytes

Channel 1
The control and status bytes for channel 1 are shown below.

Channel 2, channel 3 and channel 4
The control and status bytes of channels 2, 3 and 4 are structured like the control and status byte of channel 1.

Process data mode

Control byte 1 in process data mode

Control byte 1 (CB1) is located in the output image, and is transmitted from the controller to the terminal. In process data mode it has no function.

Bit

CB1.7

CB1.6

CB1.5

CB1.4

CB1.3

CB1.2

CB1.1

CB1.0

Name

RegAccess

-

-

-

-

-

-

-

Key

Bit

Name

Description

CB1.7

RegAccess

0bin

Register communication off (process data mode)

CB1.6 - CB1.0

-

0bin

reserved

Status byte 1 in process data mode

The status byte 1 (SB1) is located in the input image and is transmitted from terminal to the controller. In process data mode it has no function.

Bit

SB1.7

SB1.6

SB1.5

SB1.4

SB1.3

SB1.2

SB1.1

SB1.0

Name

RegAccess

-

-

-

-

-

-

-

Key

Bit

Name

Description

SB1.7

RegAccess

0bin

Acknowledgment for process data mode

SB1.6 - SB1.0

Error

0bin

reserved

Register communication

Control byte 1 in register communication

Control byte 1 (CB1) is located in the output image, and is transmitted from the controller to the terminal.

Bit

CB1.7

CB1.6

CB1.5

CB1.4

CB1.3

CB1.2

CB1.1

CB1.0

Name

RegAccess

R/W

Reg. no.

Key

Bit

Name

Description

CB1.7

RegAccess

1bin

Register communication switched on

CB1.6

R/W

0bin

Read access

1bin

Write access

CB1.5 to CB1.0

Reg. no.

Register number:
Enter the number of the register that you

  • want to read with input data word DataIN1 or
  • want to write with output data word DataOUT1.

Status byte 1 in register communication

The status byte 1 (SB1) is located in the input image and is transmitted from terminal to the controller.

Bit

SB1.7

SB1.6

SB1.5

SB1.4

SB1.3

SB1.2

SB1.1

SB1.0

Name

RegAccess

R/W

Reg. no.

Key

Bit

Name

Description

SB1.7

RegAccess

1bin

Acknowledgment for register access

SB1.6

R

0bin

Read access

SB1.5 to SB1.0

Reg. no.

Number of the register that was read or written.