KL4404 and KL4408 - Basic function principles
The KL4404 and KL4408 analog output terminals generate signals in the range 0 V to +10 V with a resolution of 12 bits (4095 steps). The outputs are single ended and have a common ground potential.
Format of the output values
In the delivery state the process data are shown in two's complement form ( -1integercorresponds to 0xFFFF). The feature register R32 can be used to select other display options (e.g. signed amount representation, Siemens format).
Output value | Output voltage | |
|---|---|---|
hexadecimal | decimal | |
0x0000 | 0 | 0 V |
0x3FFF | 16383 | +5 V |
0x7FFF | 32767 | +10 V |
Process data equations
The process data, which are transferred to the Bus Terminal, are calculated based on the following equations:
Neither user nor manufacturer scaling is active
Ydac = X x Aa + Ba | (1.0) |
Manufacturer scaling active (default setting)
Y1 = Bh + Ah x X | (1.1) |
Ydac = Y1 x Aa + Ba |
|
User scaling active
Y2 = Bw + Aw x X | (1.2) |
Ydac = Y2 x Aa + Ba |
|
Manufacturer and user scaling active
Y1 = Bh + Ah x X | (1.3) |
Y2 = Bw + Aw x Y1 | (1.4) |
Ydac = Y2 x Aa + Ba |
|
Key
X: | Controller process data |
|
Ydac: | Process data for D/A converter |
|
Ba , Aa: | Manufacturer gain and offset compensation | |
Bh , Ah: | Manufacturer scaling | |
Bw, Aw: | User scaling |
The equations of the straight line are activated via register R32.