Accessories
Fuse
Spare fuses are available as accessories. The upper of the two built-in fuses in the EL3681 is designated as a spare fuse.
WARNING
Danger for persons through electric shock!
The fuse may only be changed if the Bus Terminal is in a safe, de-energized state.
The fuse can be removed with pliers by pulling it upwards from its sockets (see Figure).
Note
Pull the fuse evenly to avoid damaging the sockets!
An improper taking out of the fuses can result in damage to the sockets!
Order number for the fuse
ZB8000-0001, pack of 10 fuses, 1.25 A