Technical data

Technical data

KL3403-... / KS3403-...

0000

0010

0014

0020

0022

0025

0026

0333

Measured values

U, I

U, I

U1)

U, I

I2)

U, I

U, I

U, I

Calculated parameters

Active power, energy, power factor (cosj)

Measuring voltage

max. 500 VAC 3~

-

max. 500 VAC 3~

Measuring voltage according to UL specifications (see UL compliance)

max. 300 VAC 3~

-

max. 300 VAC 3~

Measuring current
(continuous operation)

direct (max.)

1 A

5 A

60 mV1)

20 mA

20 mA

250 mA

1 A

333 mV (AC)

via current transformers with transformation
ratio R (max.)

R x 1 A

R x 5 A

-

R x 20 mA

R x 20 mA

R x 250 mA

R x 1 A

R x 333 mV

Voltage circuit input resistance (typical)

500 kΩ

500 kΩ

500 kΩ

500 kΩ

10 Ω2)

500 kΩ

500 kΩ

500 kΩ

Current circuit input resistance (typical)

33 mΩ

6.8 mΩ

app. 10 kΩ1)

10 Ω

10 Ω

100 mΩ

33 mΩ

40 kΩ

Resolution

16 bit (internal 21 bit)

Frequency range4

10 Hz to 500 Hz

0 Hz to 500 Hz (with deactivated DC filter and with current transformers, which support this frequency range)

Limit frequency

app. 2 kHz

Signal type

any (taking into account the frequency range and the limit frequency)

Measuring accuracy for sinusoidal current/voltage (total measuring range, based on the full scale value)

Voltage

0.5%

0.5%

0.5%

0.5%

-

0.5%

Current

0.5%
3.0%3)

1.0%
3.0%3)

-

0.5%

0.5%

0.5%

Power (calculated)

1.0%
4.0%3)

1.5%
4.0%3)

-

1.0%

-

1.0%

Measuring procedure

True RMS with 64000 samples / s

Measuring cycle time

freely configurable (50 ms per measured value pre-set)

Dielectric strength

1500 V (terminal/K-Bus)

Bit width in the input process image

72 bits inputs (3 x 8 bits status, 3 x 16 bits data)

Bit width in the output process image

72 bits outputs (3 x 8 bits control, 3 x 16 bits data)

Power supply for the electronics

via the K-bus

Current consumption from K-bus

typically 115 mA

Pluggable wiring

at all KSxxxx series terminals

Permissible ambient temperature range during operation

-25°C ... + 60°C

0°C ... + 55°C

Permissible ambient temperature range during storage

-40°C ... + 85°C

-25°C ... + 85°C

Permissible relative air humidity

95%, no condensation

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC immunity / emission

conforms to EN 61000-6-2 / EN 61000-6-4

Weight

app. 75 g

Dimensions (W x H x D)

app. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Mounting

on 35 mm mounting rail conforms to EN 60715

Installation position

variable

Protection class

IP20

Approvals / markings*

CE, UKCA, cULus, EAC

CE, UKCA, EAC

CE, UKCA, cULus, EAC

CE, UKCA, EAC

*) Real applicable approvals/markings see type plate on the side (product marking).

1) for KL3403-0014: three additional voltage circuits instead of the current circuits: 60 mV for connection of external shunts

2) for KL3403-22: three additional current circuits instead of the voltage circuits: also 20 mA

3) the measuring accuracy is reduced, if the extended temperature range is used (-25°C ... + 60°C)

4) see also chapter Additional frequency-dependent measuring error