Trigger values
Trigger unit 1
|
|
Switching threshold 1 (R41) |
Here you can specify the switching threshold for the trigger source of trigger unit 1. Scaling: Sample for KL3361: 16 mV x 1000 / 32767 = 0,488 mV |
|
Switching threshold 2 (R42) |
Here you can specify the switching threshold for enabling the trigger of trigger unit 1. | |
|
Pulse width (R43) |
Here you can specify the pulse width (tP) of trigger unit 1 for the glitch mode. The number of samples (nSP) is entered as the parameter. The pulse width thus depends on the sample rate! Sample: | |
|
valid trigger time (R44) |
Here you can specify the valid trigger time (tVT) for trigger unit 1. The number of valid samples (nVS) is entered as the parameter. The valid trigger time thus depends on the sample rate! Sample: - valid samples: nVS=100 Valid trigger time: tVT = Ts x nVS =200 µs x 100 = 20 ms | |
|
Timeframe active (R40.6) |
Here you can switch on the timeframe for trigger unit 1. |
Trigger unit 2
|
|
Switching threshold 1 (R47) |
Here you can specify the switching threshold for the trigger source of trigger unit 2. |
|
Switching threshold 2 (R48) |
Here you can specify the switching threshold for enabling the trigger of trigger unit 2. | |
|
Pulse width (R49) |
Here you can specify the pulse width for trigger unit 2. | |
|
valid trigger time (R50) |
Here you can specify the valid trigger time for trigger unit 2. | |
|
Timeframe active (R46) |
Here you can switch on the timeframe for trigger unit 2. |
Trigger unit 3 (KL3362 only)
See Trigger unit 1.
Trigger unit 4 (KL3362 only)
See Trigger unit 2.