General settings
Operation mode
|
Pre-trigger (R32.8-10) |
Recording ceases as soon as a trigger event occurs. |
Mid-trigger (R32.8-10) |
The trigger event is the center of the recording. | |
Post-trigger (R32.8-10) |
Recording commences as soon as a trigger event occurs. | |
Fast sampling (R32.8-10) |
Operation with increased sampling rate of up to 10 µs:
| |
Trigger delay active (R32.4) |
Switches the trigger delay on. | |
Trigger delay (R52) |
A trigger delay (tTD) can be specified here. The number of skipped samples (nSTD) is entered as the parameter. The trigger delay thus depends on the sample rate! Sample: | |
Test mode active (R32.5) |
Switches the test mode on. In test mode, a ramp is output instead of converted analog values. It runs from 0 to 0x3FFF and back again. | |
Auto-trigger active (R32.6) |
Switches the auto trigger function on. With auto trigger switched on, the trigger unit is automatically activated once the preceding event has been evaluated. To this end, bit 0 is toggled in status register 1 (SR1) with each new evaluation. |
General
|
Sample rate (R35) |
Interval (Ts) between two samples (scans) in microseconds. |
Sample amount (R36) |
Number of sampling values to be recorded. A maximum of 4,000 values can be recorded. | |
Trigger frequency (R56) |
Here you can specify the trigger frequency of the timer. |
Scaling channel 1
|
User offset (R33) |
Here you can enter an offset. Scaling: Sample for KL3361: 16 mV x 100 / 32767 = 0.049 mV |
User gain (R34) |
Here you can enter the gain factor for scaling the input value by this factor. |
Scaling channel 2 (KL3362 only)
|
User offset (R33) |
Here you can enter an offset. Scaling: Sample for KL3361: 16 mV x 100 / 32767 = 0.049 mV |
User gain (R34) |
Here you can enter the gain factor for scaling the input value by this factor. |