Connecting the KL3361

WARNING
Risk of injury through electric shock and damage to the device!

Bring the Bus Terminals system into a safe, de-energized state before starting mounting, disassembly or wiring of the Bus Terminals.

Connecting the KL3361 1:
Connecting the KL3361

The diagram shows the connection of four strain gauges (SG) as a bridge circuit, with supply of the measuring bridge

  • through the oscilloscope terminal (left) or
  • from an external voltage source Uext (right).

Terminal point

No.

Connection

+ 24 V

1

Supply voltage for digital output

OUT 24 V

2

Digital output

UB+

3

Input for differential voltage of the measuring bridge

UV+

4

5 V supply voltage for the strain gauges in a bridge circuit or
reference input for the external supply voltage of the measuring bridge

24 V Trigger

5

Trigger input

0V

6

Ground for trigger input

UB-

7

Input for differential voltage of the measuring bridge

UV-

8

0 V supply voltage for the strain gauges in a bridge circuit or
reference input for the external supply voltage of the measuring bridge

Supply of the measuring bridge via KL3361

The total resistance of the measuring bridge should be dimensioned in such a way that the current to be supplied by the oscilloscope terminal at the terminals UV+ and UV- never exceeds 20 mA.

Supply of the measuring bridge from an external voltage source

Note the following if the measuring bridge is supplied from an external voltage source:
The external supply voltage

  • must also be applied to the UV+ and UV- connections for reference;
  • must be within the range +5 V to +10 V;
  • must not vary by more than ±5% during operation.
    Fluctuations of the external supply voltage increase the measurement error!
    After changing the external supply voltage, the oscilloscope terminal has to be restarted for re-balancing!

The internal voltage source switches off automatically, as soon as an external voltage of more than 5 V is applied to the UV+ and UV- terminals of the oscilloscope terminal.