LEDs

LEDs 1:
LEDs

LED

Display

Power
(green)

ON

Power supply (5 V) available on the K-bus

OFF

No power supply (5 V) available on the K-bus

K-bus
(green)

ON

Data transmission on the K-bus is active

OFF

Data transmission on the K-bus is not active

Calibr.
(green)

ON

Calibration active

OFF

  • Test active (if Measure LED not lit) or
  • Measurement active (if Measure LED is lit)

Measure
(green)

ON

Measurement active (process data are valid)

OFF

  • Calibration active (if LED Calibr. is lit) or
  • Test active (if Calibr. LED not lit)

Diff.
(green)

ON

  • Differential signal is calibrated (if Calibr. LED is lit) or
  • Differential signal is checked (if LED Calibr. not lit)

Ref.
(green)

ON

  • Reference signal is calibrated (if Calibr. LED is lit) or
  • Reference signal is checked (if LED Calibr. not lit)

Err. Diff.
(red)

ON

  • Channel 1 (strain gauge differential signal) is above the valid range (max. 0xFFFF)
  • Internal reference voltage for channel 1 is missing

Err. Ref
(red)

ON

  • Channel 2 (strain gauge reference signal) is above the valid range (max. 0xFFFF)
  • Internal reference voltage for channel 2 is missing
  • Channel 2 is less than about 1 V
  • No communication with the A/D converter.
  • Actual value from the test is outside the specified tolerance range