Register overview

These registers exist once for each channel

Address

Name

Default value

R/W

Storage medium

R0

Raw ADC value

variable

R

RAM

R1…R5

reserved

0x0000

R

 

R6

Diagnostic register

variable

R

RAM

R7

Command register - not used

0x0000

R

 

R8

Terminal type

e.g. 3312

R

ROM

R9

Software version number

0x????

R

ROM

R10

Multiplex shift register

0x0218/0130

R

ROM

R11

Signal channels

0x0218

R

ROM

R12

Minimum data length

0x0098

R

ROM

R13

Data structure

0x0000

R

ROM

R14

reserved

0x0000

R

 

R15

Alignment register

variable

R/W

RAM

R16

Hardware version number

0x????

R/W

SEEROM

R17

Hardware compensation: Offset

specific

R/W

SEEROM

R18

Hardware compensation: Gain

specific

R/W

SEEROM

R19

Manufacturer scaling: Offset

0x0000

R/W

SEEROM

R20

Manufacturer scaling: Gain

0x00A0

R/W

SEEROM

R21

Hardware compensation: Reference temperature

specific

R/W

SEEROM

R22…R30

reserved

0x0000

R/W

SEEROM

R31

Code word register

variable

R/W

RAM

R32

Feature register

0x01006

R/W

SEEROM

R33

User scaling: Offset

0x0000

R/W

SEEROM

R34

User scaling: Gain

0x0100

R/W

SEEROM

R35…R63

reserved

0x0000

R/W