Register overview

These registers exist once for each channel

Address

Name

Default value

R/W

Storage medium

R0

Raw ADC value

variable

R

RAM

R1

Unprocessed ADC value for the leads

variable

R

 

R2

reserved

0x0000

R

 

R3

…

…

…

…

R5

reserved

0x0000

R

 

R6

Diagnostic register

variable

R

RAM

R7

Command register not used

0x0000

R

 

R8

Terminal type

e.g., KL3224

R

ROM

R9

Software version number

0x????

R

ROM

R10

Multiplex shift register

0x0218/0130

R

ROM

R11

Signal channels

0x0218

R

ROM

R12

Minimum data length

0x0098

R

ROM

R13

Data structure

0x0000

R

ROM

R14

reserved

0x0000

R

 

R15

Alignment register

variable

R/W

RAM

R16

Hardware version number

0x????

R/W

SEEROM

R17

Hardware compensation: Offset

specific

R/W

SEEROM

R18

Hardware compensation: Gain

specific

R/W

SEEROM

R19

Manufacturer scaling: Offset

0x0000

R/W

SEEROM

R20

Manufacturer scaling: Gain

0x00A0

R/W

SEEROM

R21

Offset register two-wire connection method

specific

R/W

SEEROM

R22

reserved

0x0000

R/W

SEEROM

R3

…

…

…

…

R30

reserved

0x0000

R/W

SEEROM

R31

Code word register

variable

R/W

RAM

R32

Feature register

0x0106

R/W

SEEROM

R33

User scaling: Offset

0x0000

R/W

SEEROM

R34

User scaling: Gain

0x0100

R/W

SEEROM

R35

reserved

0x0000

R/W

SEEROM

R36

reserved

0x0000

R/W

SEEROM

R37

Filter constant

0x0138

R/W

SEEROM

R38

reserved

0x0000

R/W

SEEROM

R3

…

…

…

…

R63

reserved

0x0000

R/W

SEEROM