KL3202 as resistance input 0 to 1 kΩ
If the KL3202 is used for resistance measurements, the following values should be written into the following registers:
• R32: Feature register: 0xF401
i.e. user scaling active with display of the measured value in Ohm and two-wire connection.
• R33: User scaling - offset (0x0000)
• R34: User scaling - gain (0x0010)
the display of the measured value follows:
Resistance in Ω |
Output value |
---|---|
0 |
0 |
1000 |
1000 |