Settings
The dialog mask for the parameterization of the KL3172 can be found under Settings.
Operation mode
Channel disabled (R32.11)
Here you can disable this channel, in order facilitate a faster cycle time for the other channel (default: not disabled).
Disabling of a channel is indicated by its Run and error LEDs going out.
Manufacturer scaling active (R32.1)
You can activate manufacturer scaling here (default: deactivated).
Signed amount representation (R32.3)
You can activate the signed amount representation here (default: deactivated).
Differential measurement (R32.6)
You can deactivate the differential measurement here (default: activated).
Stabilization of calibration active (R32.7)
You can deactivate the stabilization of the calibration here (default: activated).
Limitation of the measuring range active (R32.8)
You can deactivate the limitation of the measuring range here (default: activated).
Register values
User gain (R34)
You can specify the user gain between 0 and 65535 here (default: 256, corresponding to a factor of 1).
Calibration interval (R40)
You can specify the calibration interval for the reference signal here in steps of 100 ms (default: 300 s).
Forced calibration interval (R44)
You can specify the interval for the forced calibration here. This interval is always a multiple (default: 3dez) of the calibration interval. The interval for forced calibration when the terminal leaves the factory is therefore 3 x 180 s = 900 s.
Number of stable measured values (R47)
You can specify the number of measured values used for the calibration here (default: 50).
Tolerance for measured value stability (R48)
You can specify the stable measured value tolerance for the calibration here (default: 5).
Filter constant (R37.11-R37.4)
The filter constant SF specifies the 3dB limit frequency of the sinc3 filter (default: 860dec).
Fast-Step Mode(TM) enabled (R37.0)
You can activate Fast Step Mode here (default: deactivated). A fast reaction to jumps at the input follows in fast step mode, in spite of the filter stage being active. In this case the filter is bypassed!