Technical data
Technical data | KL3142-0000, KS3142-0000 | KL3152-0000, KS3152-0000 |
|---|---|---|
Number of inputs | 2 | |
Signal current | 0 ... 20 mA | 4 ... 20 mA |
Internal resistance | 100 Ω measuring resistance | |
Common-mode voltage UCM | ±10 V | |
Resolution | 16 bit | |
Conversion time | 140 ms, configurable | |
Measuring error (full measuring range) | ±0.05% of the full scale value, self-calibration | |
Bit width in the K-Bus I/O | 2 x 16 bit user data (optionally 2 x 8 bit control/status) | |
Bit width in the input process image | 2 data words, 2 status byte | |
Bit width in the output process image | 2 data words, 2 control byte | |
Power supply for the electronics | via the K-bus | |
Current consumption from K-bus | typically 85 mA | |
Surge voltage resistance | 35 VDC | |
Electrical isolation | 500 V (differential input / K-bus) | |
Connection | spring-loaded system | |
Pluggable wiring | for all KSxxxx terminals | |
Weight | approx. 70 g | |
Dimensions (W x H x D) | approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm) | |
on 35 mm mounting rail conforms to EN 60715 | ||
Permissible ambient temperature range during operation | 0°C ... + 55°C | |
Permissible ambient temperature range during storage | -25°C ... + 85°C | |
Permissible relative air humidity | 95%, no condensation | |
Vibration / shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27 | |
EMC immunity / emission | conforms to EN 61000-6-2 / EN 61000-6-4 | |
Protection class | IP20 | |
Installation position | variable | |
Approval/Markings* | CE, UKCA, cULus, EAC, ATEX | |
*) Real applicable approvals/markings see type plate on the side (product marking).
Ex marking
Standard | Marking |
|---|---|
ATEX | II 3 G Ex nA IIC T4 Gc |