Technical data
Technical Data | KL3011/ | KL3021/ | KL3012/ | KL3022/ |
|---|---|---|---|---|
Number of inputs | 1 | 2 | ||
Signal current | 0 mA to 20 mA | 4 mA to 20 mA | 0 mA to 20 mA | 4 mA to 20 mA |
Technology | Differential input | |||
Internal resistance | 85 Ω + diode voltage 0.7 V | |||
Common-mode voltage UCM | 35 V max. | |||
Resolution | 12 bit | |||
Conversion time | ~ 1 ms | ~ 2 ms | ||
Measuring error (total measuring range) | < ±0.3 % of the full scale value | < ± 0.30 % (at 0 °C to +55 °C) | ||
Surge voltage resistance | 35 VDC | |||
Electrical isolation | 500 V (K-Bus / signal voltage) | |||
Power supply for the electronics | via the K-Bus | |||
Current consumption from the K-bus | typically 60 mA | |||
Bit width in the K-bus I/O | Input: 1 x 16 bits of data (1 x 8 bit control/status optional) | Input: 2 x 16 bits of data (2 x 8 bit control/status optional) | ||
Configuration | No address or configuration settings | |||
Pluggable wiring | or all KSxxxx Bus Terminals | |||
Weight | approx. 70 g | |||
Dimensions (W x H x D) | approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm) | |||
on 35 mm mounting rail conforms to EN 60715 | ||||
Permissible ambient temperature range during operation | 0°C ... + 55°C | -25°C ... +60°C (extended temperature range) | ||
Permissible ambient temperature range during storage | -25°C ... + 85°C | -40°C ... +85°C | ||
Permissible relative air humidity | 95%, no condensation | |||
Vibration / shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27, see also Installation instructions for enhanced mechanical load capacity | |||
EMC immunity / emission | conforms to EN 61000-6-2 / EN 61000-6-4 | |||
Protection class / Installation position | IP20 / variable | |||
Approvals / markings | CE, UKCA, GL, cULus, EAC, ATEX | CE, UKCA, GL, cULus, EAC, ATEX | ||
Ex markings
Standard | KL3011/ | KL3021/ | KL3022/ | KL3012/ |
|---|---|---|---|---|
ATEX | II 3 G Ex nA IIC T4 Gc | II 3 G Ex nA IIC T4 Gc | ||
IECEx | - | Ex nA IIC T4 Gc | ||
cFMus | - | Class I, Division 2, Groups A, B, C, D | ||