IECEx - Special conditions

WARNING

Observe the special conditions for the intended use of Beckhoff fieldbus components in potentially explosive areas!

  • For gas: The equipment shall be installed in a suitable enclosure providing a degree of protection of IP54 according to IEC 60079-15, taking into account the environmental conditions under which the equipment is used!
  • For dust (only the fieldbus components of certificate no. IECEx DEK 16.0078X Issue 3):
    The equipment shall be installed in a suitable enclosure providing a degree of protection of IP54 according to EN 60079-31 for group IIIA or IIIB and IP6X for group IIIC, taking into account the environmental conditions under which the equipment is used!
  • The equipment shall only be used in an area of at least pollution degree 2, as defined in IEC 60664-1!
  • Provisions shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 119 V!
  • If the temperatures during rated operation are higher than 70°C at the feed-in points of cables, lines or pipes, or higher than 80°C at the wire branching points, then cables must be selected whose temperature data correspond to the actual measured temperature values!
  • Observe the permissible ambient temperature range for the use of Beckhoff fieldbus components in potentially explosive areas!
  • The individual terminals may only be unplugged or removed from the Bus Terminal system if the supply voltage has been switched off or if a non-explosive atmosphere is ensured!
  • The connections of the certified components may only be connected or disconnected if the supply voltage has been switched off or if a non-explosive atmosphere is ensured!
  • Address selectors and ID switches may only be adjusted if the supply voltage has been switched off or if a non-explosive atmosphere is ensured!
  • The front hatch of certified units may only be opened if the supply voltage has been switched off or a non-explosive atmosphere is ensured!

Standards

The fundamental health and safety requirements are fulfilled by compliance with the following standards:

Marking

Beckhoff fieldbus components that are certified in accordance with IECEx for use in areas subject to an explosion hazard bear the following markings:

Marking for fieldbus components of certificate no. IECEx DEK 16.0078X Issue 3:

 

IECEx DEK 16.0078 X

Ex nA IIC T4 Gc

Ex tc IIIC T135°C Dc

 

 

Marking for fieldbus components of certficates with later issues:

 

IECEx DEK 16.0078 X

Ex nA IIC T4 Gc