Technical data

KL2798-0000

Connection technology

2-wire

Number of outputs

8 make contacts

Rated load voltage

0 … 30 VAC/DC (only ohmic load: 0 … 48 VDC)

Peak current

max. 2 A per channel (∑ 10 A)

Breakdown voltage

80 V

Peak current

5 A (100 ms), < 50 A (10 ms)

Short circuit current

not short-circuit-proof, see peak current

Reverse voltage protection

–

Isolation voltage (channel/channel)

< 200 V

Electrical isolation

500 V (K-bus/field potential)

Switching on speed

typ. 1.8 ms, max. 5 ms

Switching off speed

typ. 30 ms, max. 50 ms

On-resistance

typ. 0.03 Ω

Current consumption power contacts

–

Current consumption K-bus

80 mA

Bit width in the process image

8 output bits

Special features

substitute for relay contacts, potential-free

Dimensions (W x H x D)

app. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Weight

app. 50 g

Mounting

on 35 mm mounting rail according to EN 60715

Permissible ambient temperature range at operation

   0 … +55°C

Permissible ambient temperature range for storage

-25…+85°C

Permissible relative air humidity

95 %, no condensation

Vibration/shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC immunity / emission

conforms to EN 61000-6-2 / EN 61000-6-4

Installation position

variable

Protection class

IP20

Approvals / markings

CE, cULus