Functional description

Load types

Load

100,000 switching cycles with

30,000 switching cycles with

Incandescent lamps

1.25 kW

2.5 kW

Fluorescent lamps

uncompensated

1.2 kW

2.5 kW

parallel compensated

650 W / 70 µF

1.3 kW / 140 µF

Fluorescent lamps in duo circuit

2 x 1.2 kW

2 x 2.5 kW

Halogen lamps (230 VAC)

1.2 kW

2.5 kW

Low-voltage halogen lamp with transformer

500 VA

500 VA

Mercury vapor/sodium vapor lamps

uncompensated

1 kW

2 kW

parallel compensated

1 kW / 70 µF

2 kW / 140 µF

Dulux lamps

uncompensated

800 W

1.6 kW

parallel compensated

560 W / 70 µF

1.1 kW / 140 µF

Operation modes

Example

Functional description 1:Fig.8: KL2641 - Example

Standards

The relay conforms to the international standards according to IEC and EN 61810 Part 1 / VDE 0435 Part 201 as well as the requirements for short-term overcurrents and protection against short-circuit according to IEC and EN 61036 / 61037.