Technical data
| Technical data | KL2631 / KS2631 | 
|---|---|
| Number of outputs | 1 make contact for power contact | 
| Nominal voltage | 400 VAC / 300 VDC | 
| DC switching capacity | 300 V = 0.15 A; 24 V = 5 A; non-linear | 
| AC switching capacity | 1500 VA | 
| Min. switching voltage | Power contact | 
| Load type | ohmic, inductive, lamp load | 
| Output current | max. 2 A | 
| Switching current | DC switching capacity: 300 V = 0.15 A; 24 V = 5 A; non-linear | 
| Electrical isolation | 500 V (K-bus / field voltage) | 
| Current consumption power contacts | load only | 
| K-Bus current consumption | 80 mA | 
| Bit width in process image | 2 outputs | 
| Switching cycles mech. (min.) | 1 x 107 | 
| Switching cycles electr. (min.) | 1.3 x 105 (2 A / 250 VAC) | 
| Configuration | no address or configuration settings required | 
| Special features | 400 V contact | 
| Pluggable wiring | for all KSxxxx terminals | 
| Weight | approx. 85 g | 
| Dimensions (W x H x D) | 15 mm x 100 mm x 70 mm (width aligned 12 mm) | 
| on 35 mm mounting rail conforms to EN 60715 | |
| Permissible ambient temperature during operation | 0 °C ... +55 °C | 
| Permissible ambient temperature during storage | -25 °C ... +85 °C | 
| Permissible relative humidity | 95 %, no condensation | 
| Vibration / shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27 | 
| EMC immunity / emission | conforms to EN 61000-6-2 / EN 61000-6-4 | 
| Installation position | variable | 
| Protection class | IP20 | 
| Approvals / markings* | CE, UKCA, EAC, DNV | 
*) Real applicable approvals/markings see type plate on the side (product marking).