Register overview
The registers serve the parameterization of the pulse width current terminal. They can be read or written by means of register communication.
|
Register no. |
Comment |
Default value |
R/W |
Memory | ||
|---|---|---|---|---|---|---|
|
Status word |
0x0000 |
0dec |
R |
RAM | ||
|
Set position (only on the KL2545) |
0x0000 |
0dec |
R/W |
RAM | ||
|
Coil voltage (only on the KL2545) |
0x0000 |
0dec |
R |
RAM | ||
|
Power supply voltage (only on the KL2545) |
e.g. 0x0030 |
e.g. 48dec |
R |
RAM | ||
|
R4 |
reserved |
- |
- |
- |
- | |
|
Temperature (only on the KL2545) |
e.g. 0x0023 |
e.g. 35dec |
R |
RAM | ||
|
Status byte |
e.g. 0x0010 |
e.g. 16dec |
R |
RAM | ||
|
Command register |
0x0000 |
0dec |
R/W |
RAM | ||
|
Terminal type |
KL2535: |
0x09E7 |
2535dec |
R |
ROM | |
|
KL2545: |
0x09F1 |
2545dec | ||||
|
Firmware version |
e.g. 0x3141 |
e.g. 1AASCII |
R |
ROM | ||
|
R10 |
Multiplex shift register |
0x0130 |
304dec |
R |
ROM | |
|
R11 |
Signal channels |
0x0218 |
536dec |
R |
ROM | |
|
R12 |
Minimum data length |
0x1818 |
6168dec |
R |
ROM | |
|
R13 |
Data structure |
0x0004 |
4dec |
R |
ROM | |
|
R14 |
reserved |
- |
- |
- |
- | |
|
R15 |
Alignment register |
0x7F80 |
32640dec |
R/W |
RAM | |
|
Hardware version number |
e.g. 0x0000 |
e.g. 0dec |
R/W |
EEPROM | ||
|
R17 |
reserved |
- |
- |
- |
- | |
|
... |
... |
... |
... |
... |
... | |
|
R30 |
reserved |
- |
- |
- |
- | |
|
Code word register |
0x0000 |
0dec |
R/W |
RAM | ||
|
Feature register |
0x0000 |
0dec |
R/W |
EEPROM | ||
|
User scaling - offset |
0x1000 |
4096dec |
R/W |
EEPROM | ||
|
User scaling - gain |
0x0000 |
0dec |
R/W |
EEPROM | ||
|
User's switch-on value |
0x0000 |
0dec |
R/W |
EEPROM | ||
|
Maximum output current |
KL2535: |
0x03E8 |
1000dec |
R/W |
EEPROM | |
|
KL2545: |
0x0DAC |
3500dec | ||||
|
Dithering - Frequency |
0x0000 |
0dec |
R/W |
EEPROM | ||
|
Dithering amplitude |
0x0000 |
0dec |
R/W |
EEPROM | ||
|
Dithering - Switch-off ramp |
0x0000 |
0dec |
R/W |
EEPROM | ||
|
Overlap threshold value |
0x0000 |
0dec |
R/W |
EEPROM | ||
|
Overlap output value |
0x0000 |
0dec |
R/W |
EEPROM | ||
|
Bend compensation -threshold value |
0x0000 |
0dec |
R/W |
EEPROM | ||
|
Bend compensation - output value |
0x0000 |
0dec |
R/W |
EEPROM | ||
|
Area compensation - threshold value |
0x03E8 |
1000dec |
R/W |
EEPROM | ||
|
Process data ramp (rising) |
0x0000 |
0dec |
R/W |
EEPROM | ||
|
Process data ramp (falling) |
0x0000 |
0dec |
R/W |
EEPROM | ||
|
R47 |
reserved |
|
|
|
| |
|
R63 |
reserved |
|
|
|
| |