IO Error Action

Action to be performed if a fieldbus error occurred.

Note: To activate a new IO error Action setting a device reset has to be performed either by executing a power cycle to the ILxxxx-B520 or by executing a Reset Service (Service Code 5) to the ILxxxx-B520 Identity Object (Class Id 1, Instance 1).

Value

Description

0

Leave local IO Cycle

1

Leave local IO Cycle and reset outputs (default)

2

freeze outputs